SPARC[tm] T3-4 Server: Hardware Specifications

Processor
Number Two or Four SPARC T3 16-Core 1.65GHz processors
Architecture SPARC V9 architecture
CPUs
  • 1.65GHz 16-Core
  • 512 threads max
  • Sixteen floating-point units per processor, one per core
  • 10 Gigabit Ethernet integrated into chip
  • On-board cryptography with new Kasumi Bulk algorithm, supporting 12 embedded security industry-standard ciphers:
    DES, 3DES, AES, RC4, SHA1, SHA256, SHA384, SHA512, MD5, RSA to 2048 key, ECC, CRC32
Cache memory 6MB integrated L2
Main Memory
Capacities
  • Total DIMM slots: 64
  • DIMM type: DDR3
  • DIMM size: 4GB or 8GB
  • Minimum Configuation: 128GB (32 × 4GB)
  • Maximum capacity: 512GB (64 × 8GB)
Standard Integrated Interfaces
Network 4 × 10/100/1000 Mbps autonegotiating ports
Up to 8 × optional 10 GbE XAUI connections
Network Management One dedicated 10/100Base-T RJ-45 port Ethernet port
Note: This port does not support connections to Gigabit networks.
Serial Management One dedicated RJ-45 port
An additional serial mangemant port is located on the main module and is
accessible from the front panel.
Remote Management Onboard system processor, running Integrated Lights Out Manager (ILOM) 3.0
Graphics One DB-15 VGA connector
USB Front: 2 USB 2.0 Ports
Rear: 2 USB 2.0 Ports
PCI Expansion Slots 16 PCI-Express Gen2 slots
Internal Mass Storage
Disks
  • Up to eight 2.5-inch SAS drives
  • 300GB 2.5-inch SAS disk drives
  • RAID 0 and RAID 1 support
Power Supplies
4 × 2060 Watt, hot-swappable, 2+2 redundant power supply units (PSU)
Environment
Input Voltage 200 - 240 VAC, 50-60Hz (VAC tolerance +/- 10%)
Input Current 12.6 A @ 200 VAC max
Input Power 2400 W @ 200 VAC max
Heat Output 7030 BTU/hr
Temperature

Operating: 5° C to 35° C (41° F to 95° F)
Nonoperating: -40° C to 65° C (-40° F to 149° F)

Note: Above 900m (3000 ft), decrease maximum temperature as altitude increase, 1° C/300m (1.6° F/1000ft)

Humidity Operating: 10% to 90% relative humidity noncondensing, 27° C (80.6° F) maximum wet bulb
Nonoperating: 93% relative humidity noncondensing, 38° C (100.4° F) maximum wet bulb
Altitude Operating: 0m to 3000m (10000 ft.)
Nonoperating: 0m to 12000m (40000 ft.)
Vibration Operating: 0.15G (x-axis), 0.10G (x,y axes) 5-500Hz swept sine
Nonoperating: 0.5G (x-axis), 0.25G (x,y axes) 5-500Hz swept sine
Shock Operating: 3Gs, 11ms half-sine
Nonoperating: 1-inch roll-off free fall, front-to-back rolling direction, 25mm threshold height at 0.75 m/s impact velocity
Acoustic Noise Operating/Idling: 8.2 B (LwAd, 1B = 10dB)
Operating/Idling: 68.2dB (LpAm, bystander positions)
Regulations
Meets or exceeds the following requirements:
Safety EN 60950-1:2006 + A11:2009, IEC 60950-1:2005, 2nd Edition, UL 60950-1, 2nd Edition, CSA C22.2 No. 60950-1-07
RFI/EMI EN55022:2006 + A1:2007 Class A, EN55024:1998 + A1:2001 + A2:2003, EN61000-3-2:2006, EN61000-3-3:1995 + A1:2001 + A2:2005, 47CFR15 Subpart B (FCC) Class A, EN300386:2005 (V1.3.3) for Telecommunication Centers and for Other Than Telecommunications Centers, ICES-003 Class A, AS/NZS CISPR22:2006 Class A, CISPR22:2008: Class A
Immunity EN55024, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11
Regulatory Markings CE, FCC, ICES-003, C-tick, VCCI, GOST-R, BSMI, MIC, UL/cUL, UL/S-mark
European Union Directives 2006/95/EC (73/23/EEC) Low Voltage Directive, 2004/108/EC (89/336/EEC) EMC Directive, 2002/96/EC Waste Electrical and Electronic Equipment (WEEE) Directive, 2002/95/EC Restriction of Hazardous Substances (RoHS) Directive
Dimensions and Weight
Height 219 mm (8.62 in.)
Width 445 mm (17.5 in.)
Depth 700 mm (27.65 in.)
Weight Appx 79 kg (175 lbs) max
Clearance and Service Access
Front 910 mm (36 in.)
Rear 910 mm (36 in.)