Sun System Handbook - ISO 3.4 June 2011 Internal/Partner Edition | |||
|
AC Input Module Power Requirements
Operating RangeNominal Voltage: 208, 220, 230, or 240 Volts ACOperating Voltage: Single Phase 180-264 Volts AC Frequency: 48-63 Hz Current: 24 A maximum AC Input Power PlugU.S. power cords have a NEMA L6-30P input plug to two IEC320-C19 output plugs. International power cords have a Blue, IEC 309, 2-Pole, 3-Wire, 32 Amp input plug, with Ground at the 6-hour position to two IEC320-C19 output plugs.AC Input ConnectorsThere are two IEC 320 C20 receptacles on the AC Input Module.NEMA L6-30R / ANSI C73.75 230 Volt Power Receptacle30 Amp, 250V, 2-pole, 3-wire, Single Phase, Grounded
IEC 309 240 Volt Power Receptacle32 Amp, 240V, 2-pole, 3-wire, Single Phase, Grounded
| ||||||||||||
|